12. Remote Configuration API (Downlink)

This guide documents the structure and mapping of configuration commands that can be sent remotely to the ISURLOG device via Downlink messages (e.g., through LoRaWAN downlinks or specific NB-IoT commands). The commands utilize a binary structure, processed by the accompanying Python library, IsurlogLPP.py.

Note

This is the full list of parameters the firmware supports over downlink — it doesn't necessarily match 8. Reference Configuration Parameters. Page 8 documents only what IsurDASH currently lets you configure through its UI; the ISURLOG firmware can support more parameters than IsurDASH currently exposes. Where the IsurDASH Configurable column says Yes, it links to the corresponding section of page 8.

Configuration Parameter Reference (config_types)

This comprehensive table defines all available remote configuration functions, their unique type code, data size, and scaling factors for encoding values.

Function Name Type (Hex) Size (Bytes) Multiplier Range (Min/Max) IsurDASH Configurable Description / Equivalent Parameter
Global Parameters
setLatencyTime A0 1 1 1-255 Yes Sets the time (minutes) between reading cycles.
setRtcSync A1 1 1 0-1 Yes Sets whether readings occur at fixed clock-synchronized intervals (1, e.g. 14:00, 14:05, 14:10 for a 5-min latency) or at intervals relative to power-on time instead (0).
setRegisterMode A2 1 1 0-1 Yes Sets Logging Mode (0=Fixed, 1=Conditional).
setRegisterAccumulator A3 1 1 0-255 Yes Sets the number of records to accumulate before sending.
setMagnetWakeup A4 1 1 0-1 No Enables/Disables the magnetic switch wake-up feature.
setDebugLED A5 1 1 0-1 No Enables/Disables the STATUS LED on the PCB.
setMaxPayloadSize 8E 1 1 0-255 Yes Sets the payload size.
setBatteryInputSoC 8F 1 1 0-1 No Enables/Disables logging of battery State of Charge.
setBatteryInputCRate 90 1 1 0-1 Yes Enables/Disables logging of the battery's charge/discharge rate.
setVDCVoltage 91 1 1 0-24 Yes Sets the sensor supply voltage.
setContinuousMode 83 1 1 0-1 No Enables/Disables Continuous Mode. When enabled, the ISURLOG keeps reading sensors without sleeping between readings — filling as many reading cycles as fit in the time available until the next transmission — instead of the fixed number of cycles set by Loop Cycles. Overrides setLoopCycles.
setLoopCycles 84 1 1 0-255 No Sets the number of readings taken per record, averaged together (used for analog-type inputs — Analog, Modbus, PT100). Ignored when Continuous Mode is enabled.
Wireless Communications (BLE-only)
setLoRaWANDevEUI A6 8 1 N/A Yes Sets the LoRaWAN Device EUI.
setLoRaWANAppEUI A7 8 1 N/A Yes Sets the LoRaWAN Application EUI.
setLoRaWANAppKey A8 16 1 N/A Yes Sets the LoRaWAN Application Key.
setAPN 93 Variable 1 N/A Yes Sets the NB-IoT/LTE-M APN.
setExternalSIM 94 1 1 0-1 Yes Toggles between the integrated eSIM and an external Nano-SIM.
setConPreference 95 1 1 0-2 Yes Sets the NB-IoT/LTE-M connection preference: 0 = Automatic (not fully supported by the firmware yet — currently falls back to NB-IoT), 1 = LTE-M, 2 = NB-IoT.
setMaxRetryCon A9 1 1 1-10 No Sets the maximum number of connection retry attempts.
setWiFiSSID 96 Variable 1 N/A Yes Sets the Wi-Fi network SSID.
setWiFiPsswd 97 Variable 1 N/A Yes Sets the Wi-Fi network password.
setLoRaWANClass 98 1 1 0-2 Yes Sets the LoRaWAN device class (A/B/C).
setMQTTIP 99 Variable 1 N/A Yes Sets the MQTT broker IP/hostname.
setMQTTPort 9A Variable 1 N/A Yes Sets the MQTT broker port.
setMQTTUser 9B Variable 1 N/A Yes Sets the MQTT username.
setMQTTPasswd 9C Variable 1 N/A Yes Sets the MQTT password.
setMQTTBaseTopic 9D Variable 1 N/A Yes Sets the MQTT base topic.
setSignalData 9E 1 1 0-1 Yes Enables/Disables logging NB-IoT signal quality (RSRQ/RSRP).

Important

In IsurDASH, the parameters in the Wireless Communications (BLE-only) section above can only be changed locally over Bluetooth (see 8.2 Wireless Communications Parameters) — this protects against a bad remote configuration leaving the ISURLOG unreachable. However, the firmware itself does not reject these same type codes if they arrive over a WiFi, LoRaWAN, or NB-IoT downlink — IsurDASH simply never sends them that way. If you are integrating downlink configuration into a third-party SCADA or backend, keep this in mind: nothing in the firmware stops you from sending these over the air, only IsurDASH's own UI restricts it.

Function Name Type (Hex) Size (Bytes) Multiplier Range (Min/Max) IsurDASH Configurable Description / Equivalent Parameter
Analog Input Configuration
setAnalogPreAcquisition AA 2 1 0-65535 Yes Sets pre-acquisition time (ms) for analog inputs.
setAnalogInputEnable AB 1 1 0-1 Yes Enables/Disables the Analog Input.
setAnalogInputZero AC 2 100 -327.68 to 327.67 Yes Sets the 4mA engineering value (scaled by 100).
setAnalogInputFullScale AD 2 100 -327.68 to 327.67 Yes Sets the 20mA engineering value (scaled by 100).
setAnalogInputLow AE 2 100 -327.68 to 327.67 Yes Sets the Low Alarm threshold (scaled by 100).
setAnalogInputHigh AF 2 100 -327.68 to 327.67 Yes Sets the High Alarm threshold (scaled by 100).
setAnalogInputLowCond B0 1 1 0-1 Yes Enables/Disables Low Alarm conditional transmission.
setAnalogInputHighCond B1 1 1 0-1 Yes Enables/Disables High Alarm conditional transmission.
Digital Input Configuration
setDigitalEnable B2 1 1 0-1 Yes Enables/Disables the Digital Input.
setDigitalCounter B3 1 1 0-1 Yes Enables/Disables Digital Input Counter Mode.
setDigitalPulseWeight B4 1 1 0-255 Yes Sets the Pulse Value/Weight (e.g., 10 liters/pulse).
setDigitalWake B5 1 1 0-255 Yes Sets the number of pulses required to wake the device.
setDigitalLow B6 1 1 0-255 Yes Sets the Low Alarm threshold.
setDigitalHigh B7 1 1 0-255 Yes Sets the High Alarm threshold.
setDigitalLowCond B8 1 1 0-1 Yes Enables/Disables Low Alarm conditional transmission.
setDigitalHighCond B9 1 1 0-1 Yes Enables/Disables High Alarm conditional transmission.
Modbus Configuration (Base)
setModbusPreAcquisition BA 2 1 0-65535 Yes Sets pre-acquisition time (ms) for Modbus inputs.
setModbusInputEnable BB 1 1 0-1 Yes Enables/Disables the Modbus Input.
setModbusInputSlaveAddress BC 1 1 0-255 Yes Sets the Modbus Slave Address.
setModbusInputRegisterAddress BD 2 1 0-65535 Yes Sets the Register Address to read.
setModbusInputFc BE 1 1 0-255 Yes Sets the Modbus Function Code (FC).
setModbusInputNumberOfDecimals BF 1 1 0-255 Yes Sets the number of decimal places for scaling.
setModbusInputIsFP C0 1 1 0-1 Yes Enables/Disables Floating Point (IEEE754) decoding.
setModbusInputInvert C1 1 1 0-1 Yes Enables/Disables Inverse Offset Mode.
setModbusInputOffset C2 2 100 -327.68 to 327.67 Yes Sets the Modbus reading Offset (scaled by 100).
setModbusInputLow C3 2 100 -327.68 to 327.67 Yes Sets the Low Alarm threshold (scaled by 100).
setModbusInputHigh C4 2 100 -327.68 to 327.67 Yes Sets the High Alarm threshold (scaled by 100).
setModbusInputLowCond C5 1 1 0-1 Yes Enables/Disables Low Alarm conditional transmission.
setModbusInputHighCond C6 1 1 0-1 Yes Enables/Disables High Alarm conditional transmission.
Modbus Configuration (Advanced)
setModbusInputBaudrate FF 1 1 0-255 Yes Sets the Modbus Baudrate.
setModbusInputDataBits 80 1 1 0-255 Yes Sets the Modbus Data Bits.
setModbusInputStopBits 81 1 1 0-255 Yes Sets the Modbus Stop Bits.
setModbusInputParity 82 1 1 0-255 Yes Sets the Modbus Parity.
PT100 Configuration
setPT100Enable C7 1 1 0-1 Yes Enables/Disables the PT100 Input.
setPT100Wires C8 1 1 2-4 Yes Sets the number of wires (2, 3, or 4).
setPT100Low C9 2 100 -327.68 to 327.67 Yes Sets the Low Alarm threshold (scaled by 100).
setPT100High CA 2 100 -327.68 to 327.67 Yes Sets the High Alarm threshold (scaled by 100).
setPT100LowCond CB 1 1 0-1 Yes Enables/Disables Low Alarm conditional transmission.
setPT100HighCond CC 1 1 0-1 Yes Enables/Disables High Alarm conditional transmission.
Internal T/H Sensors (BME680/SHT30)
setINTTHEnable CD 1 1 0-1 Yes Enables/Disables the internal temperature and humidity sensor.
setINTTHTemperatureLow CE 2 100 -327.68 to 327.67 Yes Sets the Low Temp Alarm threshold (scaled by 100).
setINTTHTemperatureHigh CF 2 100 -327.68 to 327.67 Yes Sets the High Temp Alarm threshold (scaled by 100).
setINTTHTemperatureLowCond D0 1 1 0-1 Yes Enables/Disables Low Temp Alarm conditional transmission.
setINTTHTemperatureHighCond D1 1 1 0-1 Yes Enables/Disables High Temp Alarm conditional transmission.
setINTTHHumidityLow D2 2 100 -327.68 to 327.67 Yes Sets the Low Humidity Alarm threshold (scaled by 100).
setINTTHHumidityHigh D3 2 100 -327.68 to 327.67 Yes Sets the High Humidity Alarm threshold (scaled by 100).
setINTTHHumidityLowCond D4 1 1 0-1 Yes Enables/Disables Low Humidity Alarm conditional transmission.
setINTTHHumidityHighCond D5 1 1 0-1 Yes Enables/Disables High Humidity Alarm conditional transmission.
External T/H Sensors (BME280/680)
setEXTTHEnable 85 1 1 0-1 Yes Enables/Disables the External T/H Sensor.
setEXTTHTemperatureLow 86 2 100 -327.68 to 327.67 Yes Sets the Low Temp Alarm threshold (scaled by 100).
setEXTTHTemperatureHigh 87 2 100 -327.68 to 327.67 Yes Sets the High Temp Alarm threshold (scaled by 100).
setEXTTHTemperatureLowCond 88 1 1 0-1 Yes Enables/Disables Low Temp Alarm conditional transmission.
setEXTTHTemperatureHighCond 89 1 1 0-1 Yes Enables/Disables High Temp Alarm conditional transmission.
setEXTTHHumidityLow 8A 2 100 -327.68 to 327.67 Yes Sets the Low Humidity Alarm threshold (scaled by 100).
setEXTTHHumidityHigh 8B 2 100 -327.68 to 327.67 Yes Sets the High Humidity Alarm threshold (scaled by 100).
setEXTTHHumidityLowCond 8C 1 1 0-1 Yes Enables/Disables Low Humidity Alarm conditional transmission.
setEXTTHHumidityHighCond 8D 1 1 0-1 Yes Enables/Disables High Humidity Alarm conditional transmission.
Internal Accelerometer (LIS2DH12)
setAccelEnable 00 1 1 0-1 Yes Enables/Disables the internal accelerometer.
setAccellowCond 01 1 1 0-1 No (coming soon) Enables/Disables Low Alarm conditional transmission (per axis, via channel).
setAccelhighCond 02 1 1 0-1 No (coming soon) Enables/Disables High Alarm conditional transmission (per axis, via channel).
setAccelLow 03 2 100 -327.68 to 327.67 Yes Sets the Low Alarm threshold, in g (per axis, via channel).
setAccelHigh 04 2 100 -327.68 to 327.67 Yes Sets the High Alarm threshold, in g (per axis, via channel).